| Operating voltage | 230 V AC |
| Frequency | 50 - 60 Hz |
| Installation type | Flush-mounted |
| Stand-by consumption | ~0.1 W |
| Glow lamp load | 30 mA |
| Setting range time | 0.5 - 20 min |
| Type of connection | 3-/4-conductors |
| 3/4-way conductors | Automatic |
| Secondary switching | At once |
| Type of contact | NO contact |
| Opening width | < 3 mm (µ) |
| Switching output | Not potential-free (230 V) |
| Incandescent/halogen lamp load | 1800 W |
| Fluorescent lamp load (conventional) lead-lag circuit | 1200 VA |
| Fluorescent lamp load (conventional) parallel-corrected | 580 VA 54 µF |
| Energy saving lamps | 110 W |
| LED lamp < 2 W | 20 W |
| LED lamp 2-8 W | 250 W |
| LED lamp > 8 W | 250 W |
| Fluorescent lamp load (electronic ballast) | 200 VA |
| Fluorescent lamp load (conventional) series-corrected | 1200 VA |
| Fluorescent lamp load (conventional) not corrected | 1200 VA |
| Switching capacity | 6 AX at 230 V AC, cos φ = 0.3, 10 A at 230 V AC, cos φ = 1 |
| Switch-off pre-warning | |
| Multi-voltage input | |
| Zero-cross switching | |
| Test approval | VDE |
| Housing and insulation material | High-temperature resistant, self-extinguishing thermoplastic |
| Ambient temperature | -25°C ... 45°C |
| Protection class | II |
| Type of protection | IP 20 |