| Operating voltage | 24 V AC/DC SELV |
| Output | 3 x 0-10 V, 2 x relay 5 A/250 V AC |
| Measuring range CO2 | 0 - 5000 ppm |
| Measuring range temperature | 5°C ... 40°C |
| Measuring range humidity | 30 - 80 % rF |
| ON/OFF thresholds | 700 ppm ±200 ppm, 1300 ppm ±200 ppm |
| Type of connection | Screw terminals |
| Display | 6 LEDs |
| Installation type | Wall installation (also on flush-mounted socket possible) |
| Type of protection | IP 20 |
| Protection class | II according to EN 60 730-1 |
| Operating instructions | AMUN 716 SR (3,7 MB) | |